Conventional Fire Alarm Control Panel Alarm System

Specification:Conventional Fire Alarm Control Panel Alarm SystemMain power: AC220V± 15%,50Hz/ AC110V± 15%,60Hz  Battery: DC 24V (2 x 12V 3.3Ah) Zone and sounder end of line resistors: 3.9KΩ,1W Zone monitoring current:20mA Zone short current:>110mA Zone voltage: 24V±2V Sounder alarm output: 3 x 300mA (max)/24VDC Auxiliary Supply: 300mA/24V Dimensions: 290 x 87.5 x 211.5mm One set of fault relay contacts: Rated at 0.5A SELV Humidity: ≤95%RH Number of zones: 1,2,4 weight: 2100g (without battery) Features:• The CF800X panel is available on 1,2,4 zones.• Each zone has a maximum capacity of 50 devices.• It has 3 groups of sounders output circuits each capable of supplying 300mA.• It has a 24V/300mA auxiliary supply.• It has a set of fault relay contacts,rated at 0.5A SELV.• It has the ability to disable any zone,any group of sounder.• The panel will send a fault signal when there is zone short/open or sounder short/open.• It has the ability to disconnect the zones and sounders automatically when there is zone short or sounder short.   After the short is clear, the zones and sounders will recover.• It has the sounder start/stop and delay facility (the delay time is 30-120 seconds in 30 seconds increments).• It has the "rst "re alarm and subsequent "re alarm functions.  The indicator of the "rst "re zone is #ashing and the subsequent"re zone is lit.• It has the mains-lost silence function.After con"gure the mains lostsilence function,the panel will not send the main power lost fault signal.  Related Products Company Information/* January 22, 2024 19:08:37 */!function(){function s(e,r){var a,o={};try{e&&e.split(",").forEach(function(e,t){e&&(a=e.match(/(.*?):(.*)$/))&&1