QDW3 Air circuit-breakers(ACB) OverviewQDW3 series
universal Air circuit breaker(hereinafter referred to as breaker)is
suitable for the circuit of AC 50Hz with rated voltage 400V,
690V and rated current up to 6300A. It is mainly used to
distribute electric energy and protect circuits and power-supply
equipment from overload, under-voltage, short-circuit and
single-phase earthing. with intelligentized and selective
protection functions, the breaker can improve the reliability of
power supply, and avoid unnecessary power failure. The breaker is
applicable for power stations, factories, mines(for 690V) and
modern high-buildings, especially for thedistribution system of
intelligentized building. This breaker conforms to IEC60947-2 and
GB14048.2 and CE. Size A, B and C;From 400 A to 6300
A.Applications and functions Incoming-feeder and
outgoing-feeder function in distribution systemsSwitching and
protecting large powers, motors, capacitors, generators,
transformers, busbars and cablesOverload protectionShort-time
delayed short-circuit protectionInstantaneous short-circuit
protectionUsed in building, industry, energy and
infrastructuresFeaturesModular designComponents like auxiliary
releases, motorized operating mechanisms, electronic releases,
current sensors, auxiliary circuit signaling switches, automatic
reset devices, interlocks and engagement operating mechanisms can
all be exchanged or retrofitted in the back ground, thus allowing
the circuit breaker to be adapted to new, changing
required. Communication The use of modern
communication-capable circuit breakers opens up completely new
possibilities in terms of start-up, parameterization, diagnostics,
maintenance and operation. This allows varieties of ways of
reducing costs and improving productivity in industrial plants,
buildings and infrastructure projects. Easy wiring by
different terminals A wide variety of terminals are offered,
to guarantee an optimal solution for connection to the power
circuit under different applications. Technical
specifications Standard: IEC 60947-2Number of poles: 3-pole,
4-poleRated operational voltage Ue: 400 V, 690 VRated insulating
voltage Ui: 1000 VRated frequency: 50 - 60 HzRated impulsed
withstand voltage Uimp: 12 kVNeutral pole current-carrying capacity
for 4-pole CBs: 100% InVersion: Fixed version, Withdrawable
versionFeature details:○ Measurement and operation
monitoringReal-time measurement of the power grid operating
parameters, such as: frequency power factor active power: real-time
indication of operating status, such as: fault status, alarm status
system self-diagnostic status, normal operation.○ Query
functionRunning parameter query, protection parameter setting value
query, history fault record query, self-diagnosis fault information
query and power grid measurement parameter query and other
functions.○ Parameter setting functionThe following protection
parameters can be set directly on the front panel of the
controller: current value and time value of long-time overload
protection, inverse current value of short-circuit short delay
protection, definite time current value and time value,
instantaneous protection current value, Current value and time
value, N phase protection setting value, grounding current or
residual current protection current value, time value and inverse
time coefficient, unbalance value and time value of current
unbalance protection, harmonic influence coefficient.The following
operations can be performed on the front panel of the controller:
System clock adjustment (only when this function is selected), and
tuning the internal parameters of the system that can be set by all
programmer (without programmer, but need password).○ Programming
interface functionIt provides the interface with the programmer. It
can modify some specific parameters, such as the function setting
of signal output contact, the way of voltage measurement, system
clock, protection characteristic curve, thermal memory function,
communication address and communication baud rate.○ Communication
network function (this function is only available for H type
function controller)Controller provides standard RS485 interface,
Modbus or Profibus-DP or DeviceNet protocol can be used to achieve
data transmission to meet the different monitoring system "four
remote" requirements.○ Test functionTest function sub-instantaneous
tripping simulation test and non-tripping simulation test two
kinds:(1) instantaneous trip simulation test: circuit breaker can
be instantaneous action of the tripping test, after the action can
display the circuit breaker's inherent action time.(2) non-tripping
simulation test: select the simulation test current system for
non-tripping test, alternately after the test shows the test
current and the test current in the system delay time and
simulation test fault category.○ Self-diagnosis functionThe
controller itself appears some fault diagnosis alarm.○ Fault clock
function (optional)Used to record the time of
Related products about Low Voltage Intelligent Air Circuit Breaker
- Waste Tyre Plastic Recycling Machinery Machine Tire Crusher Production Line Rubber Crumb Grinding Machine Equipment Tire Shredder
- Stretch Plastic Blowing Pet Bottle Making Blow Molding Machine Bottles Stretch Automatic Pet Bottle Blowing Machine
- Waste Plastic Pet Bottle, Water Bottle Flake, PP/HDPE/LDPE PE Film Jumbo Woven Bags Plastic Crusher Machine, Plastic Crushing Washing Recycling Machine
- Type 2 Wall-Mounted Electric Car Charging Station 7kw /11 Kwelectric Vehicle Charging Station Home Wallbox AC EV Charger Single Phase or 3three Phase
- G-View G12W Wholesale Auto Car LED Headlight Bulb High Power H13 H11 9005 H7 H4 Car LED Headlights LED Car Lights
- New Design Porcelain Round Plates Dinner Set for Wedding and Banquet
- China 2023 New Design Super Soft 100% Polyester Microfiber Knitted Oversized Decoration Hoodie Blanket
- Handmade Art Creative Materials Thickened White Paper Cup DIY Disposable Handmade Colored Paper Cup