Split Core Current Transformer with 1000A/0.333V

The H-CT005 Series are split-core current transformers. The CT can be mounted to existing panels, such as control centers or load centers, to measure or monitor wattage. These current transformer's can be mounted without removing existing cables for easier installation.1, Electrical Specifications1), Rated Primary Current(AMP. ) 50/60Hz: 1000A(0.01~1200A max)2), Turn ratio: Np: Ns=1000: 13), Current Ratio: 1000A/0.333V4), D. C. Resistance at 20 º C: 1.5Ω MAX5), Accuracy @RL=1VA: 0.5%6), Phase error at rated current range: ≤ 0.5°7), Operating Temperature Range: -40~70º C8), Storage Temperature Range: -45~85º C9), Dielectric Withstanding Voltage(Hi-pot): 3.5KV/1mA/1min10), Impulse Withstand Voltage: 5KV Peak11), Insulation Resistance: DC500V/100MΩ Min2, Applications.A, Portable/Curret instruments.B, Sub-metering.C, Monitor Motor Loads3, FeatureA, Small size.B, Low costC, High secondary turns.D, Secure locking hingsE, Full RoHS compliantF, Mounting easy.4, Package(with carton)1), 1piece per one small box(dimension(L*D*H): 16.6*16.6*7.5cm)2), 60pieces per biggest box(dimension(L*D*H): 36*30*39cm)3), Gross weight of biggest box around 17Kg.       Model Primay currentSeconadary currentLoad resistance    AccuracyDiameter  H-CT005-5080D    600A             5A  2.5VA0.5Class   50*80mm  H-CT005-5080D 1000A             5A/1A7.5VA/10VA0.5/1.0Class   50*80mm  H-CT005-5080D 1200A             5A/1A7.5VA/10VA0.5/1.0Class   50*80mm