Aisle containment in the data center requires that cabinets are
aligned in a hot aisle/cold aisle layout. Containment panels or
strips create a partition to isolate either the server supply air
(cold aisle containment) or the exhaust air (hot aisle
containment). Preventing the supply and exhaust air from mixing
significantly increases the capacity and cooling efficiency of the
cooling infrastructure.Each site will be different due to the site
conditions, cooling infrastructure, rack density and other factors.
If properly installed you can expect 20-50% reduction in cooling
costs. Efficiency is maximized if the cooling systems with variable
speed fans and there is a good return air path.Cold aisle
containment door:Glass door, excellent light pass performanceMetal
door, made of metal for better securityManual sliding door, doors
can be slide by hand to left and right, saving the limited space in
data centre.Manual hinged door, doors can be easily opened towards
outside and inside.Automatic sliding door, easy to access by
sensorAppearance and structure1. Containment top panel has even
roof structure, 350mm higher than cabinet top, top panel total
width is 1305mm, modular frame design, easy to installation.2. The
net height of aisle container is above 2 meters when the top panel
dropped away, so the daily maintenance will not be affected.3.
Thanks to the modular designed cold aisle containment units, every
unit can be installed independently and easily connected with the
units in next.4. Doors should be installed at the front and rear to
prevents the hot airflow enter into the equipment.5. Pre-installed
terminal block is connected with fire suppression systems, the
active containment ceiling panel will open when there is a fire
alarm signal.Components of containment ceiling panelUnder normal
operation time, the ceiling panels are stuck by electro-magnet in a
horizontal position, in case there is a fire alarm, ceiling panel's
electro-magnet will be cut off, panel will open due to it's gravity
to make sure the extinguish gas can enter into the cold aisle
containment.1. The ceiling panels are made from steel frame and
tempered glass, the thickness of steel frame is more than 1.5mm,
thickness of glass is more than 5mm, light pass rate is more than
99%.2. All the panels has width of 600mm, each unit can be
installed independently and connected to the next one.3. All the
panels are stuck by electro-magnet, panels will be opened when
there is a fire alarm, sensor action time is less than 3 seconds,
he panels occupies at least 60% volume against the whole cold aisle
containment. /* January 22, 2024
19:08:37 */!function(){function s(e,r){var
a,o={};try{e&&e.split(",").forEach(function(e,t){e&&(a=e.match(/(.*?):(.*)$/))&&1
Related products about Hot Aisle Cold Aisle Containment Indoors Data Center
- Waste Tyre Plastic Recycling Machinery Machine Tire Crusher Production Line Rubber Crumb Grinding Machine Equipment Tire Shredder
- Stretch Plastic Blowing Pet Bottle Making Blow Molding Machine Bottles Stretch Automatic Pet Bottle Blowing Machine
- Waste Plastic Pet Bottle, Water Bottle Flake, PP/HDPE/LDPE PE Film Jumbo Woven Bags Plastic Crusher Machine, Plastic Crushing Washing Recycling Machine
- Type 2 Wall-Mounted Electric Car Charging Station 7kw /11 Kwelectric Vehicle Charging Station Home Wallbox AC EV Charger Single Phase or 3three Phase
- G-View G12W Wholesale Auto Car LED Headlight Bulb High Power H13 H11 9005 H7 H4 Car LED Headlights LED Car Lights
- New Design Porcelain Round Plates Dinner Set for Wedding and Banquet
- China 2023 New Design Super Soft 100% Polyester Microfiber Knitted Oversized Decoration Hoodie Blanket
- Handmade Art Creative Materials Thickened White Paper Cup DIY Disposable Handmade Colored Paper Cup