HX-DP normally open siphon failure valve structure can be divided
into water chamber, air chamber, main and secondary electromagnetic
operating mechanism and electrical control box. The water chamber
part is connected with the water main pipeline, the air chamber is
connected with the atmosphere, the main and auxiliary
electromagnetic manipulator is installed on the left and right
sides of the valve, and the electrical control box is configured
and installed in the nearest place according to the specific design
requirements. After the valve electrical control module is
energized, the main and secondary electromagnetic operating
mechanism is under the action of the magnet suction, this time the
valve spindle moves, the two valve disc rubber seal rings installed
on the spindle and the two valve seats are sealed, then the
atmosphere of the water chamber and the air chamber is cut off to
form a siphon. Valve electrical control module power off, the
electromagnet immediately separated, in the energy storage spring
driving action, the two valve disc on the main shaft move to the
right, at this time the valve and the seat quickly separated, due
to the negative pressure vacuum in the main pipeline, the
atmosphere through the air cavity rapid flooding into the chamber
and the main pipe interconnect, destroy the siphon phenomenon, to
achieve water separation.Q&A1. What is a siphon water pipeline?
A low water level water source to the high water level of the water
supply, both sides of the pipe are submerged in the water, in the
water transmission process does not contact the atmosphere of the
water transmission way, called siphon water transmission channel.
2. Is siphon water transfer more energy saving than direct water
transfer? Siphon water transmission can save more than 30% of
energy, because siphon water transmission in the process of water
transmission is not required energy consumption (in theory), only
need to pump water at the start of the need for energy consumption,
water in the vacuum water transmission process is a flow, do not
need energy consumption. 3. Why install the siphon damage valve?
Siphon damage valve is a very important equipment, which is ignored
by everyone. If the siphon path does not have a quick opening
siphon break valve, it is fatal to the pump station. If the siphon
failure valve does not open the valve in time, let the atmosphere
enter the mother pipe, destroy the siphon phenomenon, high water
level water to flow into the pump, the pump impeller to turn, will
cause the water wheel escape event, resulting in huge economic
losses. 4. Where is the correct installation position of the siphon
damage valve? The siphon failure valve is installed in the position
of 15 degrees before the water outlet of the water pipeline,
because this position is the place where the pipeline air gathers,
as long as the valve is installed in this place is one of the
guarantee factors for rapid cut-off. 5, how to choose the right
type of siphon failure valve? According to the theoretical
calculation, the siphon failure valve only needs to take 5-10% of
the transverse load area of the main pipeline, which can destroy
the siphon phenomenon. HXDP pressure balance siphon damage valve
only need to take 5% of the transverse load area of the main pipe
pipe is 1400mm, its transverse load area is 0.7*0.7*3.14=1.54
Siphon damage valve 1.54*5%=0.08 Valve selection: DN= *2*1.15=367mm
siphon damage of the transverse load area of 5% Energy consumption
rate 0.15%HXQP pneumatic siphon damage valve only need to take the
main pipe of the transverse load area of 8% pipe is 1400mm, Its
transverse load area is 0.7*0.7*3.14=1.54 siphon damage valve
1.54*6%=0.093 Valve selection: DN= *2*1.15= 6% of the transverse
load area of 395mm siphon damage Energy consumption rate 0.15%HXZP
self-reliant siphon damage valve only needs to take 10% of the
transverse load area of the mainpipe pipe is 1400mm, Its transverse
load area is 0.7*0.7*3.14=1.54siphon damage valve
1.54*10%=0.154Valve selection: DN= *2=510mmsiphon damage transverse
load area 10%Energy consumption rate 0.15%6, siphon damage valve
can replace siphon type water pipe other equipment?Siphon water
supply pipeline cut-off is 2 ways, they are compared as follows. A,
a quick gate (butterfly valve) cut-off. If the butterfly valve is
selected, the pipe needs to be equipped with the same caliber
butterfly valve and damped check valve, and it also needs to be
equipped with maintenance accident gate. When the pump stops, the
water flow to the turn check valve is closed, so that the flow can
be cut off. B, one is the siphon break valve cut off. When the pump
stops, open the siphon failure valve, the air enters the pipeline,
and the vacuum can be cut off. The valve repair of this system is
very troublesome and requires a lot of factory work.For the above
two cut-off modes, a small-caliber siphon break valve can replace
the large-caliber butterfly valve and check valve. This system
valve is
Related products about Hx-Dp Siphon Vacuum Break Valve
- Waste Tyre Plastic Recycling Machinery Machine Tire Crusher Production Line Rubber Crumb Grinding Machine Equipment Tire Shredder
- Stretch Plastic Blowing Pet Bottle Making Blow Molding Machine Bottles Stretch Automatic Pet Bottle Blowing Machine
- Waste Plastic Pet Bottle, Water Bottle Flake, PP/HDPE/LDPE PE Film Jumbo Woven Bags Plastic Crusher Machine, Plastic Crushing Washing Recycling Machine
- Type 2 Wall-Mounted Electric Car Charging Station 7kw /11 Kwelectric Vehicle Charging Station Home Wallbox AC EV Charger Single Phase or 3three Phase
- G-View G12W Wholesale Auto Car LED Headlight Bulb High Power H13 H11 9005 H7 H4 Car LED Headlights LED Car Lights
- New Design Porcelain Round Plates Dinner Set for Wedding and Banquet
- China 2023 New Design Super Soft 100% Polyester Microfiber Knitted Oversized Decoration Hoodie Blanket
- Handmade Art Creative Materials Thickened White Paper Cup DIY Disposable Handmade Colored Paper Cup